Access to MID equipment on your property
MID inspects poles, above and below ground transformers and other equipment on a regular basis to help reduce the possibility of power outages.
To do this, MID needs clear access to MID equipment located on your property.
Please remove plants, shrubs, fences and anything else that could block access to the equipment. MID crews will remove these if you cannot. Please note that MID will not be responsible for damage done to these items. Removing the plants and/or fences yourself means less impact on your property. If you are not sure whether or not something needs to be cleared to allow access, please call (209) 557-1529.
 |
 |
|
Required minimum clearances
Below ground transformer:
- 8 feet above the transformer, 3 feet around it.
If you place a fence over a below ground transformer, the work crew must be able to remove easily so they can have quick access and adequate work space.
Above ground transformer:
- 8 feet in front of the transformer, 3 feet on other sides.
Examples of Above Ground Transformer Clearance:
|

Ground Padmount Tansformer:
The picture above shows the bush prevents access since the padmount transformer opens from the front. An Eight-foot clearance is needed for safe working conditions. |

Ground Padmount Transformer:
The transformer pictured above has required clearance of 8 feet in front and 3 feet on all sides with nothing preventing access.
|
|